Role of hot water temperature and water system use on Legionella control in a tertiary hospital: An 8-year longitudinal study
Autores de I3PT
Participantes ajenos a I3PT
- Gavalda, L
- Quero, S
- Gutierrez-Milla, C
- Sabria, M
Abstract
Although measures to minimize Legionella colonization in sanitary hot water installations are well established, there is little evidence of their long-term effectiveness in hospital buildings. During an 8 year period, hot water in a large hospital building was sampled monthly in areas with suitable dimensioning and recirculation and in areas with dead legs and low-use taps. In the former areas, the percentage of Legioneffa-negative samples was 83.2% when the temperature was >= 55%, 64.9% when between 50.1 degrees C and 54.0 degrees C, and 51.6% when <= 50 degrees C (p for trend <0.001). In the highest temperature group, no samples with >= 10(3) cfu/L were observed. In poorly designed areas, only 44.7% of samples were negative, and 28.9% presented >= 10(3) cfu/L although reaching 55 degrees C. In these areas, multivariate analysis showed that if hot water supplies were not used daily, the risk of Legionella colonization was greater than two-fold (odds ratio: 2.84; 95% confidence interval: 1.26-6.41), and the risk of finding Legionella concentrations >= 10(3) cfu/L was more than three-fold (odds ratio: 3.18; 95% confidence interval: 1.36-7.46), regardless the temperature. These findings indicate that the effectiveness of maintaining sanitary hot water at a minimum temperature of 55 degrees C is significantly better than that at 50 degrees C for the environmental control of Legionella but only in installations with suitable dimensioning and recirculation. In installations that do not meet these conditions, high temperatures alone result in insufficient control. (C) 2018 Elsevier Ltd. All rights reserved.
Datos de la publicación
- ISSN/ISSNe:
- 0043-1354, 1879-2448
- Tipo:
- Article
- Páginas:
- 460-466
- PubMed:
- 30472548
WATER RESEARCH PERGAMON-ELSEVIER SCIENCE LTD
Citas Recibidas en Web of Science: 43
Documentos
- No hay documentos
Filiaciones
Keywords
- Legionella; Control measures; Water temperature; Hospital water network; Outlets flushing
Campos de Estudio
Cita
Gavalda L,Garcia M,Quero S,Gutierrez C,Sabria M. Role of hot water temperature and water system use on Legionella control in a tertiary hospital: An 8-year longitudinal study. Water Res. 2019. 149. p. 460-466. DOI: 10.1016/j.watres.2018.11.032.
Portal de investigación